BPPGT - NICKEL CADMIUM STORAGE BATTERY

Product Identification

Product ID:NICKEL CADMIUM STORAGE BATTERY
MSDS Date:03/05/1991
FSC:6140
NIIN:01-251-6840
MSDS Number: BPPGT

Responsible Party
SAFT AMERICA INC. POWER SOURCES DIV.
711 INDUSTRIAL BLVD
VALDOSTA, GA 31603
US

Emergency Phone: 912-247-2331

Info Phone: 912-247-2331

Cage: 09052

Contractor
SAFT AMERICA INC.
1886 VALDOSTA, GA 31602 US

Telephone: 912-247-2331

Cage: 09052

Ingredients

CADMIUM AND CADMIUM HYDROXIDE (AS ELECTRODE)

Fraction By Weight: 7 - 13%

OSHA PEL 0.2 MG/M3 AS CD

ACGIH TLV: 0.05 MG/M3 AS CD


NICKEL AND NICKEL HYDROXIDE (AS ELECTRODE)

Fraction By Weight: 23 - 30%

OSHA PEL 1.0 MG/M3 AS NI

ACGIH TLV: 1.0 MG/M3 AS NI


POTASSIUM HYDROXIDE (SARA III)

CAS: 1310-58-3

RTECS: TT2100000

Fraction By Weight: 4 - 8%

OSHA PEL C, 2 MG/M3

ACGIH TLV: C 2 MG/M3; 9293

EPA Report Quantity: 1000 LBS

DOT Report Quantity: 1000 LBS


COBALT HYDROXIDE

CAS: 1307-86-4

RTECS: GG0904000

Fraction By Weight: 0.5 - 1%

OSHA PEL 0.05 MG/M3(COBALT)

ACGIH TLV: 0.1 MG/M3

Hazards

LD50 LC50 Mixture:TLV FOR COBALT HYDROXIDE: 0.05 MG/M3.
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:YES IARC:YES OSHA:NO
Health Hazards Acute and Chronic:NONE IF BATTERY IS NOT
LEAKING/BURNING. ACUTE EXPOSURE TO FUME MAY CAUSE RESPIRATORY TRACT
IRRITATION, PULMONARY EDEMA, CHEST PAIN, COUGHING, SWEATING,
CHILLS, SHORTNESS OF BREATH, WEAKNESS. POTASSIUM HYDROXIDE CAN
BURN EYES & SKIN. CHRONICEXPOSURE MAY CAUSE KIDNEY DYSFUNCTION AND
LUNG INJURY.
Explanation of Carcinogenicity:CADMIUM & NICKEL - REASONABLY
ANTICIPATED TO BE A CARCINOGEN (NTP). NI & NI COMPOUNDS -
CARCINOGENIC TO HUMAN (IARC).
Effects of Overexposure:NONE IF BATTERY IS NOT LEAKING/BURNING. ACUTE
EXPOSURE TO FUME MAY CAUSE RESPIRATORY TRACT IRRITATION, PULMONARY
EDEMA, CHEST PAIN, COUGHING, SWEATING, CHILLS, SHORTNESS OF BREATH,
WEAKNESS. POTASSIUM HYDROXIDE CAN BURN EYES & SKIN.
CHRONICEXPOSURE MAY CAUSE KIDNEY DYSFUNCTION AND LUNG INJURY.
Medical Cond Aggravated by Exposure:PERSONS WITH PRE-EXISTING
RESPIRATORY SYSTEM DISORDERS, PROSTATE DISEASES, LIVER PROBLEMS OR
IMPAIRED KIDNEY FUNCTION MAY BE MORE SUSCEPTIBLE TO THE EFFECTS OF
THE SUBSTANCE.

First Aid

First Aid:GET MEDICAL ATTENTION IMMEDIATELY. EYE/SKIN:IMMEDIATELY FLUSH
WITH WATER FOR AT LEAST 15 MINUTES. HOLD EYELIDS OPEN.
INHALED:REMOVE TO FRESH AIR & PROVIDE OXYGEN/CPR IF NEEDED. ORAL:
GET EMERGENCY MED ICAL ATTENTION.

Fire Fighting

Flash Point:NONE
Extinguishing Media:WATER SPRAY, CARBON DIOXIDE, FOAM OR DRY CHEMICAL
FOR SURROUNDING FIRE. USE WATER SPRAY TO COOL FIRE EXPOSED
CONTAINERS.
Fire Fighting Procedures:WEAR FULL PROTECTIVE CLOTHING AND
NIOSH-APPROVED SELF-CONTAINED BREATHING APPARATUS WITH FULL
FACEPIECE OPERATED IN THE POSITIVE PRESSURE MODE.
Unusual Fire/Explosion Hazard:TOXIC METAL OXIDE FUMES MAY BE EVOLVED
DURING BURNING.

Accidental Release

Spill Release Procedures:BATTERY AND CELL CASES WILL NORMALLY CONTAIN
MATERIALS OF CONCERN. USE INDUSTRIAL ABSORBENT TO COLLECT LIQUID
POTASSIUM HYDROXIDE.
Neutralizing Agent:WEAK ACID FOR POTASSIUM, NICKEL & CADMIUM HYDROXIDE

Handling

Handling and Storage Precautions:STORAGE- AVOID BREAKING, CRUSHING OR
OTHERWISE DESTROYING THE PHYSICAL INTEGRITY OF THE CELL OR BATTERY.
Other Precautions:DO NOT INCINERATE. DO NOT TOUCH BROKEN OR LEAKING
BATTERIES. WASH THOROUGHLY AFTER HANDLING. AVOID CONTACT WITH INNER
COMPONENTS.

Exposure Controls

Respiratory Protection:USE NIOSH APPROVED SELF-CONTAINED BREATHING
APPARATUS TO PROTECT AGAINST FUMES.
Ventilation:ADEQUATE
Protective Gloves:NATURAL RUBBER IF PUNCTURED CASE
Eye Protection:SAFETY GOGGLES WITH OPTIONAL FACE SHIELD
Other Protective Equipment:EYE WASH STATION, QUICK DRENCH SHOWER AND
IMPERVIOUS CLOTHING
Work Hygienic Practices:OBSERVE GOOD PERSONAL HYGIENE PRACTICES AND
RECOMMENDED PROCEDURES. DO NOT WEAR CONTAMINATED CLOTHING.
Supplemental Safety and Health

Chemical Properties

HCC:B1
Appearance and Odor:OUTER METAL CASING CONTAINS PRISMATIC CELLS WITH
ELECTROLYTES SEALED WITHIN

Stability

Stability Indicator/Materials to Avoid:YES
STRONG ACIDS
Stability Condition to Avoid:EXCESSIVE HEAT, FIRE
Hazardous Decomposition Products:METAL OXIDE FUMES

Disposal

Waste Disposal Methods:CELLS AND BATTERIES MAY BE RETURNED AT SENDERS
EXPENSE TO A PERMITTED TREATMENT, STORAGE, DISPOSAL FACILITY
(TSDF). DISPOSAL MUST BE MADE IN ACCORDANCE WITH ALL APPLICABLE
FEDERAL, STATE AND LOCAL LAW S AND REGULATIONS.

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.